THE HIGH‑VOLTAGE HORIZON: PROS AND CONS OF 800VDC BATTERIES IN MODERN DATA CENTRES

Datacentres for better security

Share this White Papers

By Eric Hill, General Manager Product and Marketing, CSB Energy Technology 

It’s no secret that AI workloads are pushing rack power densities higher from tens of kilowatts, through hundreds, and onto thousands at megawatt scale. Legacy architecture is starting to realise physical and efficiency limits. To respond, manufacturers pairing with hyperscale operators are discussing and advancing new 800Vdc architecture, up from the traditional smaller voltage backbone of 48Vdc/400Vac. I have been asked constantly over the last 6 months what I think about this new idea for battery deployment and how it can help. To provide an opinion, it’s important to understand the tradeoffs both positive and negative and let operators decide if this new concept is a benefit to adopt.

Why is 800Vdc a Thing Now?

Physics Advantages – As well known for anyone with experience working in electricity, when you raise voltage, this lowers current for a given power output which means you can reduce copper mass and resistive losses (I²R). A recent post by AB Power shows a great real-world example: “Delivering 400 kW at 48V requires ~8,000A; at 800V, it’s ~500A—a ~94% reduction, making high‑density racks feasible in practice.”

Efficiency Improvements – By using higher voltage infrastructure, power path efficiencies can be realised. Some estimates show up to a 5% reduction in copper usage per rack as noted from a recent white paper published by Alpha and Omega Semiconductors.

Infrastructure Changes – the large players in the ecosystem like NVIDIA are already collaborating with hyperscalers on this high voltage distribution which includes BMS, relays, sensors, power converters, and others. It’s only natural this will drive innovation into the entire data centre market and force others in the industry to innovate and adapt.

The Case FOR 800Vdc Batteries

Lower Current – many white papers and technical publications on this subject from companies such as Texas Instruments, Alpha and Omega Semiconductors and others show the benefits of having lower current. High voltage slashes current, which in turn eases mechanical constraints, inherently reducing cost and installation complexity. With reduced mechanical constraints such as copper and larger gauge wiring, improvement in airflow around busbars and cabling, which translate to more effective passive and active cooling systems. AI learning power loads for batteries are mirroring similar demand-response applications seen in large-scale front-ofmeter utility power applications with multiple micro-cycling several times per event. Lower current loads on the batteries can mean potential longer service life of deployment for electrochemistry that can support micro cycling.

Higher Efficiency – Having reduced I²R losses and fewer conversion stages in power can improve facility‑level efficiency by up to 5% in emerging HVDC topologies. This is according to a recent blog post made by NVIDIA that highlights many of the power efficiencies. This means an operator can not only provide power at higher levels but do so smarter and utilise more of the gains once lost in conversion. In terms of batteries, any efficiency gain means higher capacity levels of energy available, which can make the difference in a power blip or outage.

Scalability – with all the higher power requirements, means the distribution of that power will require new levels of design to make server racks, PDU, GPU, and batteries more compact and stackable to deploy in the hundreds of racks. Using higher voltage with reduced mechanical stress means smaller footprint can be achieved. For batteries, this means smaller footprints at higher power densities where possible.

Future-State Alignment – So many different technological advancements in power design from ultracapacitors, solid state transformers, DC-DC convertors, and many others means the designers are doing all they can to simplify power paths. A recent article by Data centre Frontier highlights these advancements and how this is possible. Batteries are following a similar trend with regards to emerging options like solid state lithium-ion, sodium-ion, high power density VRLA, and fuel cells.

The Case AGAINST 800Vdc Batteries

More Safety Needed – Higher voltage directly increases the severity, likelihood, and complexity of several hasards. Greater risk of electrical shock hasard, risk of arc flash higher than AC, greater thermal runaway intensity, increased complexity of safe work procedures including more advanced lockout/tagout procedures, higher levels of battery risk assessment, and more levels of certification and training will be required. IEEE and NFPA are still working on standards to be compatible with these new ever-changing standardsf.

Immature Market – 800Vdc is still a theoretical deployment narrative with several announcements made and deployments expected to start rolling out this year and next (NVIDIA announced it will start rolling out this power architecture in 2027). It will take battery manufacturers time to catch up and develop systems that can be compatible. This means limited supply chain, longer lead times, and harder to obtain components, putting further strain on power availability and backup.

Higher Costs – with an immature market and unknown technology deployed in practice, this means higher costs are guaranteed for upfront capital requirements. New devices mean higher levels of training; this means organisational costs for not only new products, but skill development will naturally need to increase.

Legacy Integration Challenge – most of the landscape of data centre power architecture is based around 120-480Vac three-phase and anywhere from 12V – 600Vdc. Components including UPS, GPU, PDU, batteries, and many others are mainly built around those ranges. Integration of higher voltage will mean answering the age-old retrofit question of how do I future-proof my data centre for higher power. It is already an immense challenge for brownfield installations and will only get more complicated for greenfield installations.

The Ecological Consideration

Energy Use – In a recent fact sheet published by AAAS (American Association for Advancement of Science), U.S. data centres consumed ~4.4% of U.S. electricity in 2023 and are projected to reach 6.7–12% by 2028, largely driven by AI workloads. While power efficiency gains are meaningful, this may be overtaken by absolute load growth without parallel decarbonisation and demand management from all sources. 

The environmental impact isn’t limited to energy use through electricity and copper, however. As these footprints increase, efficiency gains grow, more component usage becomes the norm, awholistic approach must be taken. While using higher voltage levels does provide efficiency gains on power usage, other factors outside this scope such as water use, local noise/air impacts, siting pressures, and community effects rise with scale; battery manufacturing, resource extraction, and end‑of‑life recycling remain essential sustainability questions that data centres are partially responsible to help support. MIT published an interesting new article worth reading about this impact and how we can all contribute to operating more sustainably.

My Advice for Data centre Operators

800Vdc is not a miracle cure for underlying problems which is power availability. While this new architecture is a natural advancement, it will allow data centres to use power more effectively and will most likely result in widespread adoption to some degree, it’s sort of a kicking-the-can-downroad approach. It helps put a Band-Aid on the larger problem of power availability. The footprint growth isn’t going to slow anytime soon, and the AI demand is continuing to grow. How we generate more clean energy sources to support the infrastructure build-out should be top priority, even if it is a much more challenging problem to solve.

Do What Makes Sense – not all data centres are created equal. Use higher voltage architecture where it’s needed most. AI-dense racks for learning loads and large-scale power clusters is a start.The hyperscalers will perfect this adaptation and see if it makes sense across the board. Using traditional AC and DC voltage topologies is still widely considered acceptable, even with the increasing power load requirements. There are many efficiency gains being researched as we speak at these lower voltage levels.

The bottom line is a typical battery manufacturers answer, “It Depends”. The argument can be made both for and against. 800Vdc can lower power losses and materials, but sustained environmental progress depends on clean power procurement, responsible battery supply chains, and holistic resource planning alongside HVDC efficiency gains.

 

About CSB Energy Technology

As one of the world’s leading manufacturers and distributors of sealed lead-acid maintenance-free batteries, we work to create a sustainable society with our capability to store and utilize power and energy through our CSB acronym of Creativity, Sincerity, and Belief. We do this by providing world-class energy storage solutions for our customers through our innovative VRLA-AGM battery technology.

Our Mission For Today

We power possibilities by creating a sustainable future for all with our forward-thinking products focusing on delivery of quality power + energy storage.

Our Vision For Tomorrow

Our goal is to energize tomorrow by becoming the premier power and energy partner across the world to solve challenges through our guiding principles of Creativity, Sincerity, and Belief.

Founded in 1987, CSB now operates 6 business locations, 3 production locations and has nearly 2,300 employees worldwide. Combined with our worldwide distribution network and commitment to quality, these items have significantly contributed to our growth today. Being a member of the EnergyWith Group based in Japan, we are fully committed to the development of technology to meet the needs of the market and customers.

For further information please visit https://csb-battery.com/ or contact service@csb-battery.eu.

Visit the DATACENTRE.ME Directory Listing for CSB Energy Technology here.

 

***END***